{"id":2031,"date":"2025-02-27T19:40:33","date_gmt":"2025-02-27T11:40:33","guid":{"rendered":"https:\/\/led.amasly.com\/?p=2031"},"modified":"2025-03-06T22:24:19","modified_gmt":"2025-03-06T14:24:19","slug":"gaz-kazani-odalari-i%cc%87ci%cc%87n-elektri%cc%87kli%cc%87-patlamaya-karsi-dayaniklilik-ve-havalandirma-gerekleri%cc%87","status":"publish","type":"post","link":"https:\/\/led.amasly.com\/tr\/patlamaya-dayanikli-ekipman\/gaz-kazani-odalari-i%cc%87ci%cc%87n-elektri%cc%87kli%cc%87-patlamaya-karsi-dayaniklilik-ve-havalandirma-gerekleri%cc%87\/","title":{"rendered":"Gaz kazan\u0131 odalar\u0131 i\u00e7in elektriksel patlamaya dayan\u0131kl\u0131l\u0131k ve havaland\u0131rma gereklilikleri"},"content":{"rendered":"<h2 class=\"wp-block-heading\"><strong>1 gaz kazan\u0131 odas\u0131 patlamaya dayan\u0131kl\u0131 tasar\u0131m<\/strong><strong><\/strong><\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Petrol, gaz kazan dairesi kazan dairesi gaz reg\u00fclat\u00f6r\u00fc odas\u0131, yak\u0131t pompas\u0131 odas\u0131, p\u00fclverize k\u00f6m\u00fcr haz\u0131rlama odas\u0131, k\u00f6m\u00fcr k\u0131r\u0131c\u0131 odas\u0131 ve k\u00f6m\u00fcr ta\u015f\u0131ma koridoru gibi patlama tehlikesi olan alanlar\u0131n s\u0131n\u0131fland\u0131r\u0131lmas\u0131, mevcut \u00c7in ve Avrupa Birli\u011fi standartlar\u0131na uygun olmal\u0131d\u0131r, \u201cPatlama Tehlikeli Ortam Elektrik Tesisat\u0131 Tasar\u0131m Kodu\u201d GB50058 ilgili h\u00fck\u00fcmler; gaz kazan dairesi kazan dairesi gaz reg\u00fclat\u00f6r\u00fc odas\u0131 patlama tehlikesi olan alanlara aittir.<\/p>\n\n\n\n<div class=\"wp-block-uagb-image uagb-block-c956399c wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-none\"><figure class=\"wp-block-uagb-image__figure\"><a class=\"\" href=\"https:\/\/led.amasly.com\/tr\/\" target=\"\" rel=\"noopener\"><img decoding=\"async\" srcset=\"https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/994a24f7548f0a2e440d27327b211829-1024x695.png ,https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/994a24f7548f0a2e440d27327b211829.png 780w, https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/994a24f7548f0a2e440d27327b211829.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/994a24f7548f0a2e440d27327b211829-1024x695.png\" alt=\"\" class=\"uag-image-2032\" width=\"1080\" height=\"733\" title=\"994a24f7548f0a2e440d27327b211829\" loading=\"lazy\" role=\"img\"><\/a><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">\u201cGaz kazan\u0131 odas\u0131 g\u00fcvenlik \u00e7\u0131k\u0131\u015f\u0131 acil tahliye g\u00f6stergesi\u201d patlama tehlikesi olan alan\u0131n yak\u0131n\u0131nda veya \u00fcst\u00fcnde patlamaya dayan\u0131kl\u0131 tipte tasarlanacakt\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">A\u015fa\u011f\u0131daki ko\u015fullardan birini kar\u015f\u0131layan alanlar patlama tehlikesi olmayan alanlar olarak kategorize edilebilir: 1, sal\u0131n\u0131m kayna\u011f\u0131 yoktur ve yan\u0131c\u0131 maddelerin alana s\u0131zma olas\u0131l\u0131\u011f\u0131 yoktur.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2. Olu\u015fabilecek maksimum yan\u0131c\u0131 madde konsantrasyonu, alt patlay\u0131c\u0131 s\u0131n\u0131r de\u011ferinin y\u00fczde 10'unu a\u015fmaz.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3, \u00fcretim s\u00fcrecinde ekipman\u0131n yak\u0131n\u0131nda a\u00e7\u0131k alev kullan\u0131lmas\u0131 veya y\u00fczey s\u0131cakl\u0131\u011f\u0131n\u0131n s\u0131cak k\u0131s\u0131mlar\u0131n\u0131n ekipman\u0131n yak\u0131n\u0131ndaki alanda yan\u0131c\u0131 maddelerin tutu\u015fma s\u0131cakl\u0131\u011f\u0131n\u0131 a\u015fmas\u0131;.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">4. \u00dcretim tesisi alan\u0131 d\u0131\u015f\u0131nda, a\u00e7\u0131k havada veya havai boru hatt\u0131 b\u00f6lgesinde yan\u0131c\u0131 maddelerin ta\u015f\u0131nmas\u0131 i\u00e7in a\u00e7\u0131k bir \u015fekilde kurulmu\u015f, ancak vanas\u0131 duruma g\u00f6re belirlenir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3 maddeye g\u00f6re: gaz kazan\u0131 odas\u0131 patlama tehlikesi olmayan alana ayr\u0131labilir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Gaz s\u0131z\u0131nt\u0131s\u0131 m\u00fcmk\u00fcnd\u00fcr, konsantrasyon patlay\u0131c\u0131 limitin alt s\u0131n\u0131r\u0131n\u0131n 10%'sini a\u015ft\u0131\u011f\u0131nda, kazan dairesinin \u00e7at\u0131s\u0131na yak\u0131n alan do\u011fal gaz depolama alan\u0131d\u0131r, ayd\u0131nlatma armat\u00fcrleri ve anahtarlar patlamaya dayan\u0131kl\u0131 tipte kullan\u0131lmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Yan\u0131c\u0131 gaz ka\u00e7a\u011f\u0131 konsantrasyonu, patlay\u0131c\u0131 limitin alt s\u0131n\u0131r\u0131n\u0131n 25%'sini a\u015ft\u0131\u011f\u0131nda, sesli ve g\u00f6rsel alarm sinyalleri taraf\u0131ndan verilen gaz ka\u00e7a\u011f\u0131 alarm\u0131 ve ka\u00e7ak konsantrasyonu patlay\u0131c\u0131 limitin alt s\u0131n\u0131r\u0131n\u0131n 50%'sine ula\u015ft\u0131\u011f\u0131nda kaza egzoz fan\u0131n\u0131 ba\u015flat\u0131r, ayn\u0131 zamanda do\u011fal gaz kayna\u011f\u0131n\u0131 derhal kapat\u0131r. toplam giri\u015f solenoid valfinin gaz giri\u015f \u015febekesine, ayd\u0131nlatma armat\u00fcrlerinin ve anahtarlar\u0131n\u0131n \u00e7at\u0131s\u0131na yak\u0131n kazan dairesine, patlamaya dayan\u0131kl\u0131 tipte kaza egzoz fan\u0131 se\u00e7imi.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Gaz reg\u00fclat\u00f6r\u00fcne ek olarak gaz kazan\u0131 odas\u0131 patlama tehlikesi olan alana aittir ve elektriksel patlamaya dayan\u0131kl\u0131 tasar\u0131m i\u00e7in \u201cpatlama y\u00f6netmelikleri\u201d, gaz kazan\u0131 odas\u0131 ve biti\u015fi\u011findeki kontrol odas\u0131 ve di\u011fer yard\u0131mc\u0131 odalar ve di\u011fer elektrik tasar\u0131m\u0131 patlay\u0131c\u0131 olmayan tehlikeli alan ortam tasar\u0131m\u0131na uygun olmal\u0131d\u0131r.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\"><strong>2 gaz kazani odasi gaz g\u00fcvenli\u0307k \u00f6nlemleri\u0307<\/strong><strong><\/strong><\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">D\u0131\u015f gaz boru hatt\u0131n\u0131n kazan dairesine, g\u00fcvenli ve kullan\u0131m\u0131 kolay bir yere, acil kapatma vanas\u0131na ba\u011fl\u0131 kazan dairesi gaz konsantrasyonu alarm cihaz\u0131 ile monte edilmelidir, vana gaz bas\u0131n\u00e7 g\u00f6stergesinden sonra monte edilmelidir.<\/p>\n\n\n\n<div class=\"wp-block-uagb-image uagb-block-5683b0c2 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-none\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/9537b2036b24cf8dba0f232988fcfbf7-1024x680.png ,https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/9537b2036b24cf8dba0f232988fcfbf7.png 780w, https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/9537b2036b24cf8dba0f232988fcfbf7.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/9537b2036b24cf8dba0f232988fcfbf7-1024x680.png\" alt=\"\" class=\"uag-image-2033\" width=\"1080\" height=\"717\" title=\"9537b2036b24cf8dba0f232988fcfbf7\" loading=\"lazy\" role=\"img\"><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">Gaz boru hatt\u0131 bir bo\u015faltma borusu, numune alma portu ve bl\u00f6f portu ile donat\u0131lacak ve a\u015fa\u011f\u0131daki h\u00fck\u00fcmlere uygun olacakt\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1, konumu gaz veya hava \u00fcfleme i\u00e7indeki boru ve aksesuarlar\u0131 m\u00fcmk\u00fcn olmal\u0131d\u0131r;.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2, da\u011f\u0131l\u0131m borusu d\u0131\u015f mekana giden bir ana kur\u015funla birle\u015ftirilebilir, \u00e7\u0131k\u0131\u015f kazan dairesinin s\u0131rt\u0131ndan 2 metreden daha y\u00fcksek olmal\u0131 ve gaz\u0131n kom\u015fu binalara girmemesi ve havaland\u0131rma cihazlar\u0131n\u0131n emilmesi i\u00e7in serbest b\u0131rak\u0131lmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3, havaya g\u00f6re gaz da\u011f\u0131l\u0131m\u0131n\u0131n yo\u011funlu\u011fu, hava veya tor\u00e7 emisyonlar\u0131nda kullan\u0131lmal\u0131 ve b\u00f6lgenin g\u00fcvenlik ve \u00e7evre koruma gereksinimlerinin r\u00fczgar \u00fcst\u00fc taraf\u0131n\u0131n minimum s\u0131kl\u0131\u011f\u0131n\u0131 kar\u015f\u0131lamal\u0131d\u0131r; tesis bir tor\u00e7 havaland\u0131rma sistemine sahip oldu\u011funda, gaz\u0131 sisteme bo\u015faltmak uygundur.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.5 Gaz bo\u015faltma borusunun boru \u00e7ap\u0131, \u00fcfleme b\u00f6l\u00fcm\u00fcn\u00fcn hacmine ve \u00fcfleme s\u00fcresine g\u00f6re belirlenmelidir; \u00fcfleme hacmi, \u00fcfleme b\u00f6l\u00fcm\u00fcn\u00fcn 10 kat\u0131 ~ 20 kat\u0131 hacmine g\u00f6re hesaplanabilir; \u00fcfleme s\u00fcresi 15 dakika ~ 20 dakika i\u00e7in kullan\u0131labilir; \u00fcfleme gaz\u0131 nitrojen veya di\u011fer inert gazlar olabilir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.6 Kazan dairesi gaz borular\u0131 yan\u0131c\u0131 veya patlay\u0131c\u0131 depolar, g\u00f6rev odalar\u0131, da\u011f\u0131t\u0131m ve trafo odalar\u0131, kablo kanallar\u0131 (kuyular), asans\u00f6r \u015faftlar\u0131, havaland\u0131rma hendekleri, kanallar, bacalar ve sahan\u0131n korozif \u00f6zelliklerinden ge\u00e7memelidir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.7 Her kazan gaz borusu, gaz valfi grubunun g\u00fcvenilir performans\u0131 ile desteklenmelidir, gaz besleme bas\u0131nc\u0131ndan \u00f6nceki valf grubu ve valf grubu \u00f6zellikleri br\u00fcl\u00f6r\u00fcn maksimum y\u00fck gereksinimlerini kar\u015f\u0131lamal\u0131d\u0131r; valf grubu temel bile\u015fimi ve s\u0131ras\u0131, valf bas\u0131n\u00e7 anahtarlar\u0131ndan ve ak\u0131\u015f kontrol kelebek valflerinden \u00f6nce ve sonra kesme valfi, bas\u0131n\u00e7 g\u00f6stergesi, filtre, bas\u0131n\u00e7 reg\u00fclat\u00f6r valfi, oluklu al\u0131c\u0131, 2 seviyeli veya ka\u00e7ak tespiti i\u00e7in solenoid valflerin kombinasyonu olmal\u0131d\u0131r; Gaz boru hatt\u0131n\u0131n ate\u015flenmesi, br\u00fcl\u00f6rden gazdan \u00f6nce Trunk borusundan br\u00fcl\u00f6rden gazdan \u00f6nce 2 veya kombine ka\u00e7ak tespit solenoid valfinden \u00f6nce kullan\u0131lmal\u0131 ve seviyesinde bir kesme vanas\u0131 ve 2 solenoid valf ile donat\u0131lmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.8 Gaz besleme bas\u0131nc\u0131ndan \u00f6nce kazan gaz vanas\u0131 kapatma vanas\u0131 br\u00fcl\u00f6r\u00fcn gereksinimlerine uygun olarak belirlenmeli ve gaz vanas\u0131 besleme ak\u0131\u015f\u0131n\u0131n kalitesi aras\u0131nda 5kPa ~ 20kPa'ya ayarlanmal\u0131d\u0131r. kazan\u0131 nominal y\u00fck \u00e7al\u0131\u015fmas\u0131nda, br\u00fcl\u00f6r yanma stabilitesinde yapabilmelidir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.11 bina zemininden dikey olarak ge\u00e7en gaz boru hatt\u0131, ba\u011f\u0131ms\u0131z bir boru kuyusuna yerle\u015ftirilmeli ve d\u0131\u015f duvara kar\u015f\u0131 d\u00f6\u015fenmelidir; bina zemini boru kuyular\u0131 boyunca, her 2 veya 3 kat, yang\u0131n b\u00f6lmesinin zemin yang\u0131na dayan\u0131kl\u0131l\u0131k s\u0131n\u0131r\u0131ndan daha az olmamal\u0131d\u0131r; \u0130ki yang\u0131n b\u00f6lmesinin alt k\u0131sm\u0131na biti\u015fik olarak C S\u0131n\u0131f\u0131 yang\u0131n servis kap\u0131s\u0131 kurulmal\u0131d\u0131r; boru hatt\u0131 kuyular\u0131n\u0131n zemin kat\u0131ndaki bina yang\u0131n servis kap\u0131s\u0131n\u0131n alt k\u0131sm\u0131 elektrikle \u00e7al\u0131\u015fan bir yang\u0131n damperi ile kurulmal\u0131d\u0131r Hava giri\u015f panjuru; boru kuyular\u0131 atmosferik panjurun \u00fcst k\u0131sm\u0131nda kurulmal\u0131d\u0131r; boru kuyular\u0131 do\u011fal havaland\u0131rma kullan\u0131lmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.12 Boru kuyular\u0131ndaki gaz y\u00fckselticileri vana \u00fczerine yerle\u015ftirilmemelidir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">13.3.13 Gaz boru tesisat\u0131 ve aksesuarlar\u0131nda d\u00f6kme demir par\u00e7alar\u0131n kullan\u0131lmas\u0131 kesinlikle yasakt\u0131r; yang\u0131n b\u00f6lgesinde kullan\u0131lacak vanalar, yang\u0131na dayan\u0131kl\u0131 \u00f6zelliklere sahip olmal\u0131d\u0131r.<\/p>\n\n\n\n<h2 class=\"wp-block-heading\"><strong>3 kaza havaland\u0131rma sistemi<\/strong><strong><\/strong><\/h2>\n\n\n\n<p class=\"wp-block-paragraph\">Di\u011fer binalarda bulunan petrol, gaz kazan dairesi kazan dairesi, ba\u011f\u0131ms\u0131z hava besleme ve egzoz sistemi kurulmal\u0131, havaland\u0131rma cihaz\u0131 patlamaya dayan\u0131kl\u0131 olmal\u0131, havaland\u0131rma a\u015fa\u011f\u0131daki h\u00fck\u00fcmlere uygun olmal\u0131d\u0131r.<\/p>\n\n\n\n<div class=\"wp-block-uagb-image uagb-block-14ca1575 wp-block-uagb-image--layout-default wp-block-uagb-image--effect-static wp-block-uagb-image--align-none\"><figure class=\"wp-block-uagb-image__figure\"><img decoding=\"async\" srcset=\"https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/0798926bd3b7f0169460721fc538047f-1024x761.png ,https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/0798926bd3b7f0169460721fc538047f.png 780w, https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/0798926bd3b7f0169460721fc538047f.png 360w\" sizes=\"auto, (max-width: 480px) 150px\" src=\"https:\/\/led.amasly.com\/wp-content\/uploads\/2025\/02\/0798926bd3b7f0169460721fc538047f-1024x761.png\" alt=\"\" class=\"uag-image-2034\" width=\"1080\" height=\"803\" title=\"0798926bd3b7f0169460721fc538047f\" loading=\"lazy\" role=\"img\"><\/figure><\/div>\n\n\n\n<p class=\"wp-block-paragraph\">1, yak\u0131t olarak gaz kullan\u0131m\u0131, normal havaland\u0131rma saatte 6 kereden az olmamal\u0131, kaza say\u0131s\u0131 saatte 12 kereden az olmamal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2, kazan dairesi yar\u0131 bodrum veya yar\u0131 bodrumda kurulmu\u015ftur, normal havaland\u0131rmas\u0131 saatte 6 kereden az olmamal\u0131d\u0131r, kaza say\u0131s\u0131 saatte 12 kereden az olmamal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3, kazan dairesi yeralt\u0131nda veya bodrumda ayarlan\u0131r, saat ba\u015f\u0131na hava de\u011fi\u015fim say\u0131s\u0131 12 kattan az olmamal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">4, kazan dairesine g\u00f6nderilen toplam taze hava miktar\u0131, kazan dairesinin her saatteki hava de\u011fi\u015fim miktar\u0131n\u0131n 3 kat\u0131ndan fazla olmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">5. Kontrol odas\u0131na g\u00f6nderilen temiz hava miktar\u0131 maksimum vardiya operat\u00f6r\u00fcne g\u00f6re hesaplanacakt\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">15.3.8 Gaz reg\u00fclat\u00f6r\u00fc odas\u0131 ve patlama riski olan di\u011fer odalarda saatte en az 6 kez hava de\u011fi\u015fimi olmal\u0131d\u0131r; do\u011fal havaland\u0131rma gereksinimleri kar\u015f\u0131layamad\u0131\u011f\u0131nda, mekanik havaland\u0131rma cihazlar\u0131 kurulmal\u0131 ve kaza havaland\u0131rma cihaz\u0131n\u0131n saatte en az 12 kez hava de\u011fi\u015fimi ayarlanmal\u0131d\u0131r; havaland\u0131rma cihaz\u0131 patlamaya dayan\u0131kl\u0131 olmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">15.3.10 Mekanik havaland\u0131rma odas\u0131 emi\u015f \u00e7\u0131k\u0131\u015f yeri a\u015fa\u011f\u0131daki h\u00fck\u00fcmlere uygun olarak ayarlanmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1, gaz veya ya\u011f\u0131n ba\u011f\u0131l yo\u011funlu\u011fu 0,75'e e\u015fit veya daha az oldu\u011funda, emme \u00e7\u0131k\u0131\u015f\u0131n\u0131n konumu \u00fcst alana ayarlanmal\u0131d\u0131r, d\u00fczlemin kenar\u0131ndaki emme \u00e7\u0131k\u0131\u015f\u0131 tavana veya \u00e7at\u0131 mesafesi 0,1 m'den fazla olmamal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2 Gaz veya ya\u011f\u0131n ba\u011f\u0131l yo\u011funlu\u011fu 0,75'ten fazla oldu\u011funda, emme \u00e7\u0131k\u0131\u015f\u0131 konumu alt alana ayarlanmal\u0131d\u0131r, zemine olan mesafenin kenar\u0131n\u0131n alt\u0131ndaki emme \u00e7\u0131k\u0131\u015f\u0131 0,3 m'den fazla olmamal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">Patlama tehlikesi olan alandaki havaland\u0131rma hava ak\u0131\u015f\u0131, yan\u0131c\u0131 maddenin h\u0131zla 25% veya daha d\u00fc\u015f\u00fck patlama alt s\u0131n\u0131r de\u011ferine seyreltilmesini sa\u011flayabildi\u011finde, iyi havaland\u0131r\u0131lm\u0131\u015f olarak belirlenebilir ve a\u015fa\u011f\u0131daki h\u00fck\u00fcmlerle tutarl\u0131 olmal\u0131d\u0131r.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1 A\u015fa\u011f\u0131daki yerler iyi havaland\u0131r\u0131lan yerler olarak belirlenebilir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1) a\u00e7\u0131k hava mekanlar\u0131.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2) a\u00e7\u0131k binalarda, bina duvarlar\u0131nda, \u00e7at\u0131 a\u00e7\u0131kl\u0131klar\u0131nda, bunlar\u0131n boyutlar\u0131nda ve konumlar\u0131nda bina i\u00e7indeki havaland\u0131rman\u0131n a\u00e7\u0131k alan etkisine e\u015fde\u011fer olmas\u0131n\u0131 sa\u011flamak.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">3) Do\u011fal havaland\u0131rma i\u00e7in kal\u0131c\u0131 a\u00e7\u0131kl\u0131klar\u0131 olan a\u00e7\u0131k olmayan binalar.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">4) Kapal\u0131 alanlar i\u00e7in, dakikada taban alan\u0131n\u0131n metrekaresi ba\u015f\u0131na en az 0,3 m3 hava veya 6 kez en az lh hava de\u011fi\u015fimi sa\u011flay\u0131n.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2 Mekanik ventilasyon kullan\u0131ld\u0131\u011f\u0131nda, mekanik ventilasyon yetmezli\u011finin etkisi a\u015fa\u011f\u0131daki durumlarda hari\u00e7 tutulabilir.<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">1) kapal\u0131 veya yar\u0131 kapal\u0131 binalarda yedek bir ba\u011f\u0131ms\u0131z havaland\u0131rma sistemi sa\u011flan\u0131r; ve<\/p>\n\n\n\n<p class=\"wp-block-paragraph\">2) Havaland\u0131rma ekipman\u0131n\u0131n ar\u0131zalanmas\u0131 durumunda, otomatik alarmlar veya prosesin durdurulmas\u0131 veya ekipman\u0131n ba\u011flant\u0131s\u0131n\u0131 kesmek i\u00e7in \u00f6nlemler gibi yan\u0131c\u0131 maddelerin sal\u0131n\u0131m\u0131n\u0131n \u00f6nlenmesini sa\u011flayacak \u00f6nlemler sa\u011flan\u0131r.<\/p>","protected":false},"excerpt":{"rendered":"<p>1 gas boiler room explosion-proof design Oil, gas boiler room boiler room gas regulator room, fuel pump room, pulverized coal preparation room, coal crusher room and coal transport corridor with explosion hazardous areas such as the classification, should be consistent with the current Chinese and European Union standards, \u201cExplosion Hazardous Environment Electrical Installation Design Code\u201d [&hellip;]<\/p>\n","protected":false},"author":1,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"_uag_custom_page_level_css":"","site-sidebar-layout":"default","site-content-layout":"","ast-site-content-layout":"default","site-content-style":"default","site-sidebar-style":"default","ast-global-header-display":"","ast-banner-title-visibility":"","ast-main-header-display":"","ast-hfb-above-header-display":"","ast-hfb-below-header-display":"","ast-hfb-mobile-header-display":"","site-post-title":"","ast-breadcrumbs-content":"","ast-featured-img":"","footer-sml-layout":"","ast-disable-related-posts":"","theme-transparent-header-meta":"","adv-header-id-meta":"","stick-header-meta":"","header-above-stick-meta":"","header-main-stick-meta":"","header-below-stick-meta":"","astra-migrate-meta-layouts":"set","ast-page-background-enabled":"default","ast-page-background-meta":{"desktop":{"background-color":"var(--ast-global-color-4)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"ast-content-background-meta":{"desktop":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"tablet":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""},"mobile":{"background-color":"var(--ast-global-color-5)","background-image":"","background-repeat":"repeat","background-position":"center center","background-size":"auto","background-attachment":"scroll","background-type":"","background-media":"","overlay-type":"","overlay-color":"","overlay-opacity":"","overlay-gradient":""}},"footnotes":""},"categories":[8],"tags":[],"class_list":["post-2031","post","type-post","status-publish","format-standard","hentry","category-explosion-proof-equipment"],"uagb_featured_image_src":{"full":false,"thumbnail":false,"medium":false,"medium_large":false,"large":false,"1536x1536":false,"2048x2048":false,"trp-custom-language-flag":false},"uagb_author_info":{"display_name":"Joe","author_link":"https:\/\/led.amasly.com\/tr\/author\/jacklin\/"},"uagb_comment_info":0,"uagb_excerpt":"1 gas boiler room explosion-proof design Oil, gas boiler room boiler room gas regulator room, fuel pump room, pulverized coal preparation room, coal crusher room and coal transport corridor with explosion hazardous areas such as the classification, should be consistent with the current Chinese and European Union standards, \u201cExplosion Hazardous Environment Electrical Installation Design Code\u201d&hellip;","_links":{"self":[{"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/posts\/2031","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/users\/1"}],"replies":[{"embeddable":true,"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/comments?post=2031"}],"version-history":[{"count":2,"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/posts\/2031\/revisions"}],"predecessor-version":[{"id":2279,"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/posts\/2031\/revisions\/2279"}],"wp:attachment":[{"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/media?parent=2031"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/categories?post=2031"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/led.amasly.com\/tr\/wp-json\/wp\/v2\/tags?post=2031"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}